Voltage Drop Calculator
Enter the load, the one-way length, the voltage and the wire: get the drop in volts and percent, the smallest wire that holds your target, and how far that wire can run.
What this does not check
- It is single-phase (and DC). Three-phase drop uses √3 in place of the 2, about 13 % less for the same current and length; the FieldDojo app does not do three-phase drop on this calculator either.
- K = 12.9 for copper and 21.2 for aluminum are approximations of conductor resistance at operating temperature. Hot conductors in a hot attic run higher, and the reactance of large conductors on AC is ignored.
- The 3 % target is an informational note in the NEC, not a requirement. The tool lets you set another target; the code minimum is ampacity, which the smallest-wire answer checks against NEC 310.16 and 240.4(D).
- It sizes one circuit. Feeder drop and branch drop add: 3 % on the branch after 3 % on the feeder is 6 %, past the 5 % the notes suggest in total.
How to use it
Enter the load in amps, the length one way from the panel to the load in feet, the voltage, and the wire size you plan to pull. The big number is the drop as a percent of the source voltage, with the volts beside it.
Under it are two answers you would otherwise work out by hand. The smallest wire that holds the drop to your target and still carries the load, and how far the wire you picked can run at this load before it passes the target. Set the target to 3 % for a branch circuit, or lower if a feeder ahead of it already uses part of the 5 % total.
The method
VD = 2 × K × I × L ÷ CM
K = 12.9 copper · 21.2 aluminum · I = amps · L = one-way feet · CM = circular mils
% drop = VD ÷ source volts × 100To find the smallest wire, the same formula is solved for circular mils, then the first size in NEC Chapter 9 Table 8 at or above that minimum is picked, as long as its ampacity covers the load. That second condition is why a 30 A load on a 10 ft run still gets 10 AWG: voltage drop would allow 14 AWG, ampacity does not.
Worked examples
20 A on 12 AWG copper, 150 ft, 120 V. 2 × 12.9 × 20 × 150 ÷ 6,530 = 11.85 V, which is 9.88 %. To hold 3 % (3.6 V) the wire needs 2 × 12.9 × 20 × 150 ÷ 3.6 = 21,500 CM: 6 AWG at 26,240 CM, which drops 2.46 %.
Same circuit at 240 V. The volts lost do not change, 11.85 V, but they are half the percentage, 4.94 %. 3 % of 240 V is 7.2 V, so every run limit doubles: 12 AWG at 20 A goes 91 ft instead of 45.
Aluminum feeder, 30 A on 8 AWG, 100 ft, 240 V. 2 × 21.2 × 30 × 100 ÷ 16,510 = 7.7 V, 3.21 %. Just over 3 %; one size up, 6 AWG aluminum, brings it to 2.02 %.
Every limit on the voltage drop chart (38 ft for 14 AWG at 15 A, 45 ft for 12 AWG at 20 A, 48 ft for 10 AWG at 30 A) comes out of this calculator with the target at 3 %.
Where it goes wrong in the field
The common error is using round-trip length. The 2 in the formula is the return path; enter one-way feet or the answer doubles. The second is sizing for drop and forgetting the ground: when the conductors go up for voltage drop, NEC 250.122(B) makes the equipment ground go up in proportion. The third is stacking drops. A subpanel 3 % down a feeder leaves 2 % for every branch it feeds if you want to stay inside 5 % total.
For the full method, ampacity first and drop second, read the wire sizing and voltage drop guide.
Code references
NEC 210.19 Informational NoteBranch-circuit voltage drop, 3 % recommended (5 % feeder plus branch)2023 editionNEC 215.2 Informational NoteFeeder voltage drop, 3 % recommended (5 % feeder plus branch)2023 editionNEC Chapter 9, Table 8Conductor properties, circular mils2023 editionNEC Table 310.16 · 240.4(D)75 °C ampacity and the small-conductor caps, checked before a size is offered2023 edition
Section numbers and table values move between editions, and jurisdictions amend them. Confirm against the edition your authority having jurisdiction enforces.
Common questions
- How far can you run 12 gauge wire on a 20 amp circuit?
- 45 ft one way at full load before the drop passes 3 % at 120 V: 3.6 V × 6,530 CM ÷ (2 × 12.9 × 20 A) = 45.6 ft. At 240 V it doubles, to 91 ft. A circuit that never runs near 20 A can go further, in proportion to the load.
- What size wire for 150 feet at 20 amps?
- 6 AWG copper to stay within 3 % at 120 V: the minimum is 2 × 12.9 × 20 × 150 ÷ 3.6 = 21,500 circular mils, and 6 AWG is the first size over it at 26,240. It drops 2.46 %. 12 AWG would drop 9.88 %. Splice 12 AWG pigtails where 6 AWG will not land, and upsize the ground in proportion under NEC 250.122(B).
- Is the 3 percent voltage drop rule a code requirement?
- No. It is an informational note to NEC 210.19 for branch circuits and 215.2 for feeders: 3 % on either, 5 % for the two together. Notes are not enforceable on their own, but engineers, specs and some jurisdictions write them in, and equipment runs better inside them.
- Do I use one-way or round-trip distance?
- One way, panel to load. The 2 in the formula already counts the trip out on the hot and back on the neutral. Entering the round trip doubles the drop.
For the method behind this — worked examples, the tables, and where it goes wrong — read the full guide.