Voltage drop chart: max wire run at 3 %

How far 14, 12 and 10 AWG copper go at a full breaker load before the drop passes 3 %: 38, 45 and 48 ft one way at 120 V. Plus 20 A by gauge, what 240 V changes, and the fix where 6 AWG will not land.

Copper · 120 V single-phase · a full breaker load · one-way feet · 3 % drop (NEC informational note, not a rule)

Max one-way run at 3 % drop, copper, 120 V, full breaker load
BreakerWireMax run, one wayCode
15 A14 AWG38 ftNEC 210.19 Inf. Note · 240.4(D)
20 A12 AWG45 ftNEC 210.19 Inf. Note · 240.4(D)
30 A10 AWG48 ftNEC 210.19 Inf. Note · 240.4(D)
A 20 A circuit at 120 V, by gauge
WireMax run at 3 %, one wayCode
12 AWG45 ftNEC 210.19 Inf. Note
10 AWG72 ftNEC 210.19 Inf. Note
8 AWG115 ftNEC 210.19 Inf. Note
6 AWG183 ftNEC 210.19 Inf. Note
The long run: 20 A at 150 ft, 120 V
WireDropCode
12 AWG9.88 %VD = 2 × K × I × L ÷ CM · NEC Ch. 9 Table 8
6 AWG2.46 %VD = 2 × K × I × L ÷ CM · NEC Ch. 9 Table 8
At 240 Vevery distance above doubles3 % of 240 V is 7.2 V, twice 3.6 V
Where 6 AWG will not land12 AWG pigtails, 6 AWG groundNEC 250.122(B)
FieldDojo field sheet, max run at 3 %: 15 A 14 AWG 38 ft, 20 A 12 AWG 45 ft, 30 A 10 AWG 48 ft; 20 A at 150 ft 12 AWG 9.88 %, 6 AWG 2.46 %; 20 A by gauge 10 AWG 72, 8 AWG 115, 6 AWG 183 ft; at 240 V every distance doubles; where 6 AWG will not land, 12 AWG pigtails and a 6 AWG ground.
The wire run limits field sheet, free in the FieldDojo app to save or send. Same numbers as the table above.

How to read it

Each distance is how far the wire can run, one way, before the drop at full breaker load passes 3 % of 120 V, which is 3.6 V. One way means panel to load, not the length of copper in the wall: the formula already counts both legs, hot and neutral. Pull 45 ft of 12/2 for a 45 ft run and you are at the limit, not under it.

The numbers come from the single-phase formula every electrician learns:

VD = 2 × K × I × L ÷ CM
K = 12.9 for copper · I = amps · L = one-way feet · CM = circular mils

Solve it for L with VD set to 3.6 V and you get the table. A 20 A circuit on 12 AWG (6,530 CM): 3.6 × 6,530 ÷ (2 × 12.9 × 20) = 45.6, so 45 ft.

Why short runs fail at full load

The surprise in this chart is how short the numbers are: at 120 V and a full 30 A, even 10 AWG runs out at 48 ft, and 12 AWG on a 20 A receptacle circuit at 45 ft. The chart assumes the breaker is fully loaded, which is the worst case and the right one to design for: a circuit that is only ever half loaded drops half as much, and you can run twice as far.

Going longer

Two ways out, and the table shows both. Raise the voltage: at 240 V the allowed drop is 7.2 V, so every distance doubles. Or raise the size: a 20 A circuit reaches 72 ft on 10 AWG, 115 ft on 8 AWG and 183 ft on 6 AWG. At 150 ft, 12 AWG drops 9.88 %, more than three times the target, and 6 AWG drops 2.46 %.

A 6 AWG conductor will not land on a receptacle or switch terminal. Splice short 12 AWG pigtails at each end with a connector listed for both sizes, and upsize the equipment ground in proportion under NEC 250.122(B), which on this run means a 6 AWG ground.

For any other load, length, voltage or aluminum, run the numbers in the voltage drop calculator, or read the full method in the wire sizing and voltage drop guide.

Code references

Section numbers and table values move between editions, and jurisdictions amend them. Confirm against the edition your authority having jurisdiction enforces.