Voltage drop chart: max wire run at 3 %
How far 14, 12 and 10 AWG copper go at a full breaker load before the drop passes 3 %: 38, 45 and 48 ft one way at 120 V. Plus 20 A by gauge, what 240 V changes, and the fix where 6 AWG will not land.
Copper · 120 V single-phase · a full breaker load · one-way feet · 3 % drop (NEC informational note, not a rule)
| Breaker | Wire | Max run, one way | Code |
|---|---|---|---|
| 15 A | 14 AWG | 38 ft | NEC 210.19 Inf. Note · 240.4(D) |
| 20 A | 12 AWG | 45 ft | NEC 210.19 Inf. Note · 240.4(D) |
| 30 A | 10 AWG | 48 ft | NEC 210.19 Inf. Note · 240.4(D) |
| Wire | Max run at 3 %, one way | Code |
|---|---|---|
| 12 AWG | 45 ft | NEC 210.19 Inf. Note |
| 10 AWG | 72 ft | NEC 210.19 Inf. Note |
| 8 AWG | 115 ft | NEC 210.19 Inf. Note |
| 6 AWG | 183 ft | NEC 210.19 Inf. Note |
| Wire | Drop | Code |
|---|---|---|
| 12 AWG | 9.88 % | VD = 2 × K × I × L ÷ CM · NEC Ch. 9 Table 8 |
| 6 AWG | 2.46 % | VD = 2 × K × I × L ÷ CM · NEC Ch. 9 Table 8 |
| At 240 V | every distance above doubles | 3 % of 240 V is 7.2 V, twice 3.6 V |
| Where 6 AWG will not land | 12 AWG pigtails, 6 AWG ground | NEC 250.122(B) |
- Copper, 120 V, single-phase, a full breaker load (15, 20 or 30 A), one-way feet.
- The 3 % figure is an NEC informational note, not a rule. Your engineer, your spec or your jurisdiction may hold you to it anyway.
- Where a run is upsized for voltage drop, the equipment ground is upsized in proportion (NEC 250.122(B)): 12 AWG to 6 AWG is about four times the area, so the ground goes from 12 AWG to 6 AWG too.

How to read it
Each distance is how far the wire can run, one way, before the drop at full breaker load passes 3 % of 120 V, which is 3.6 V. One way means panel to load, not the length of copper in the wall: the formula already counts both legs, hot and neutral. Pull 45 ft of 12/2 for a 45 ft run and you are at the limit, not under it.
The numbers come from the single-phase formula every electrician learns:
VD = 2 × K × I × L ÷ CM
K = 12.9 for copper · I = amps · L = one-way feet · CM = circular milsSolve it for L with VD set to 3.6 V and you get the table. A 20 A circuit on 12 AWG (6,530 CM): 3.6 × 6,530 ÷ (2 × 12.9 × 20) = 45.6, so 45 ft.
Why short runs fail at full load
The surprise in this chart is how short the numbers are: at 120 V and a full 30 A, even 10 AWG runs out at 48 ft, and 12 AWG on a 20 A receptacle circuit at 45 ft. The chart assumes the breaker is fully loaded, which is the worst case and the right one to design for: a circuit that is only ever half loaded drops half as much, and you can run twice as far.
Going longer
Two ways out, and the table shows both. Raise the voltage: at 240 V the allowed drop is 7.2 V, so every distance doubles. Or raise the size: a 20 A circuit reaches 72 ft on 10 AWG, 115 ft on 8 AWG and 183 ft on 6 AWG. At 150 ft, 12 AWG drops 9.88 %, more than three times the target, and 6 AWG drops 2.46 %.
A 6 AWG conductor will not land on a receptacle or switch terminal. Splice short 12 AWG pigtails at each end with a connector listed for both sizes, and upsize the equipment ground in proportion under NEC 250.122(B), which on this run means a 6 AWG ground.
For any other load, length, voltage or aluminum, run the numbers in the voltage drop calculator, or read the full method in the wire sizing and voltage drop guide.
Code references
NEC 210.19 Informational NoteBranch-circuit voltage drop, 3 % recommended (5 % feeder plus branch)2023 editionNEC 240.4(D)Small-conductor overcurrent caps, 14 / 12 / 10 AWG copper at 15 / 20 / 30 A2023 editionNEC Chapter 9, Table 8Conductor properties, circular mils2023 editionNEC 250.122(B)Equipment grounding conductor increased in proportion when the circuit conductors are2023 edition
Section numbers and table values move between editions, and jurisdictions amend them. Confirm against the edition your authority having jurisdiction enforces.